What this calculator does
This calculator answers a winter question and a summer question with the same arithmetic: how much usable capacity is left when temperature moves away from room temperature. Enter the rated capacity, a measured capacity derate for the temperature, and the planned usable discharge, and the workbench returns the usable capacity in amp-hours. It is a planning tool for sizing, not a temperature model.
Short answer: around 25°C, lithium batteries are close to their rated performance. As temperature drops below freezing, usable capacity falls sharply, and as heat rises far above room temperature, short-term performance may stay high but battery ageing speeds up. A battery that feels fine at 20°C may deliver much less usable energy on a freezing morning. The practical value of Lithium Battery Temperature Effect Calculator depends on the accuracy of those inputs.
The key point is that the workbench does not prescribe a derating curve. The temperature effect must come from the particular cell or battery datasheet — the tool takes a measured derate as an input and applies it. Any page that invents a universal cold-weather percentage is guessing; this one does not. Better information usually improves a Lithium Battery Temperature Effect Calculator estimate more than extra decimal places.
The formulas behind the result
Usable capacity (Ah) = rated capacity (Ah) × (1 − temperature derate) × planned usable discharge. With the workbench defaults — 100 Ah rated, 25% derate, 80% planned discharge — that is 100 × 0.75 × 0.80 = 60 Ah usable. At 12.8 V that is 60 × 12.8 = 768 Wh of usable energy, against 1,024 Wh at room temperature with no derate.
The derate is the temperature effect, entered as a percentage. A 25% derate means the battery delivers 75% of its rated capacity at that temperature and current. The planned discharge is the share of the remaining capacity the system is allowed to use — 80% in the default case, matching the common lithium planning figure.
Heat uses a different rule of thumb, and it is about ageing rather than capacity. A common rule of thumb is that every 10°C rise above a moderate baseline can significantly accelerate ageing, so hotter operation deserves attention even when short-term capacity still looks acceptable. The workbench does not compute ageing: the heat discussion below is guidance, not a workbench output. A cautious interpretation of Lithium Battery Temperature Effect Calculator includes the relevant operating limits.
The derate also depends on how hard the battery is working, not only on the temperature. A battery that delivers 85% of its capacity at 0°C at a gentle discharge may deliver less at a high discharge rate, because the voltage sag grows with current and the usable energy falls with it. Check the datasheet derate at the actual discharge rate the system will use, not at the gentlest test condition, and remember that a warmed battery compartment or a lower discharge rate are both ways to recover capacity that a bigger battery would otherwise have to provide.
Worked example: a 100 Ah battery at 25% cold derate
Take a 12.8 V, 100 Ah LiFePO4 battery on a cold morning, with a measured derate of 25% at that temperature and current, and a planned discharge of 80%. The steps below replay the workbench calculation, then convert the usable amp-hours into watt-hours at 12.8 V so the result can be compared with the room-temperature figure.
| Step | Calculation | Result |
|---|---|---|
| Rated capacity | Given | 100 Ah |
| After 25% derate | 100 × 0.75 | 75 Ah |
| After 80% discharge | 75 × 0.80 | 60 Ah usable |
| Usable energy at 12.8 V | 60 × 12.8 | 768 Wh |
| Room-temperature usable | 100 × 0.80 × 12.8 | 1,024 Wh |
Usable capacity at different derates
The table below applies the workbench formula to a 100 Ah battery at 80% planned discharge, at four derates. The 15% and 45% rows match the cold-performance figures reported in this page's earlier version: real-world test summaries often show LiFePO4 around 85% at 0°C and near 55% at −20°C, while NMC-style lithium-ion can be a bit lower at those same cold points. Those percentages are reported summaries, not datasheet values for any specific cell, and they are flagged as such below. Record these assumptions whenever you use Lithium Battery Temperature Effect Calculator with another system.
| Temperature derate | Capacity after derate | Usable at 80% | Usable energy at 12.8 V |
|---|---|---|---|
| 0% (room temperature) | 100 Ah | 80 Ah | 1,024 Wh |
| 15% (about 0°C, LiFePO4) | 85 Ah | 68 Ah | 870 Wh |
| 25% (workbench default) | 75 Ah | 60 Ah | 768 Wh |
| 45% (about −20°C, LiFePO4) | 55 Ah | 44 Ah | 563 Wh |
Read the table as a sizing warning. At 45% derate the same 100 Ah battery delivers only 44 Ah usable — barely half its room-temperature figure — so winter planning often needs extra energy margin or a warmed battery compartment. Both Li-ion and LiFePO4 lose usable performance in the cold, but the exact drop depends on cell design, current draw and pack controls.
What each input means
Rated capacity is the battery's rated amp-hours at room temperature, under the manufacturer's stated conditions. The workbench default is 100 Ah. It is the starting point before any temperature effect is applied.
Manufacturer capacity derate is the percentage of capacity lost at the temperature being planned for, from the cell or battery datasheet or a measured test. The default is 25%. This is the input that carries all the temperature knowledge: the workbench applies it, but it does not choose it, and a guessed derate gives a guessed answer.
Planned usable discharge is the share of the remaining capacity the system plans to use, in percent. The default is 80%. It is the same depth-of-discharge planning figure used across this site's battery guides, applied after the temperature derate rather than before it. This is the uncertainty that a Lithium Battery Temperature Effect Calculator worksheet should make visible.
Reading the result — and its limits
Cold discharge and cold charging are different problems, and confusing them is the most dangerous mistake on this topic. Many manufacturers set charging limits starting at 0°C while still allowing discharge well below freezing, especially for LiFePO4. A battery that can still deliver power on a freezing morning may still be damaged by charging at the same temperature. Check the charging limit separately, on the datasheet, before planning any cold-weather charging.
Heat deserves the same separate treatment. Above 25°C, short-term capacity can look fine while ageing accelerates, so a battery that performs well in a hot summer may still lose years of life. Keep batteries out of hot enclosures and parked vehicles in summer, and treat sustained operation far above room temperature as a lifetime cost, not a free performance gain.
The calculator cannot approve a temperature plan. It takes a derate as an input and returns usable capacity; it does not verify that the derate is right for a particular cell, current and temperature. Where the number matters — winter backup, cold-climate vehicles, or any system that must work on the coldest day — use the datasheet derate for that exact cell and test the result in the real conditions. A second Lithium Battery Temperature Effect Calculator scenario can reveal whether that difference matters.
Sizing for winter means working the formula backwards from the usable capacity needed. Suppose a system needs 60 Ah usable in the cold. At a 45% derate and 80% planned discharge, the rated capacity must be 60 ÷ (0.55 × 0.80) = 136 Ah, so a 150 Ah class battery is the planning choice. At a 15% derate the same 60 Ah needs only 60 ÷ (0.85 × 0.80) = 88 Ah, so a 100 Ah battery suffices. The difference between those two answers is the whole winter sizing problem: the same load needs a battery half as large again when the cold derate doubles, and guessing the derate is the same as guessing the battery size.
Sources and verification status
Author: Saqib Jillani · Reviewer: lithiumbattery.info Editorial Team
The worked numbers on this page are arithmetic from the inputs stated beside them — every figure can be reworked with a pocket calculator. The cold-performance figures (LiFePO4 around 85% at 0°C and near 55% at −20°C; NMC-style lithium-ion a bit lower) are real-world test summaries reported in this page's earlier version, not datasheet values for any specific cell, and they still need a named source before they are relied on. The 10°C ageing rule of thumb is a planning illustration, not an exact chemistry law. The 0°C charging limit for LiFePO4 is a common manufacturer limit, stated here as a general practice rather than a figure from a named datasheet. For background on how batteries store energy, see the U.S. Department of Energy battery reference linked below.