What this calculator does
This calculator estimates how large a battery bank needs to be to run an inverter for a chosen number of hours. Enter the AC load in watts, the hours of backup you want, the DC bank voltage, the inverter efficiency and the share of the battery you plan to use. The workbench returns the required battery capacity in amp-hours.
Short answer: required amp-hours equals load watts times hours divided by battery voltage times efficiency times usable discharge. A 650 W load running for 5 hours on a 24 V bank at 88% efficiency and 80% usable discharge needs 650 × 5 ÷ (24 × 0.88 × 0.80) = 192.4 Ah. The practical value of Inverter Battery Calculator depends on the accuracy of those inputs. A cautious interpretation of Inverter Battery Calculator includes the relevant operating limits.
The formula works because the AC energy demand must be converted into the DC energy the battery bank must provide. The battery has to cover the load energy plus inverter losses, and it has to hold more than the usable share, because the unusable reserve stays in the battery. Planning from the AC load alone, without efficiency and usable discharge, understates the bank by a large margin.
The formulas behind the result
Four formulas cover everything on this page. All of them start from the AC load in watts, which is the load the inverter actually runs, not the inverter's maximum rating.
AC energy (Wh) = load (W) × hours. A 650 W load for 5 hours needs 650 × 5 = 3,250 Wh at the AC side.
DC energy (Wh) = AC energy ÷ efficiency. At 88% efficiency the battery must deliver 3,250 ÷ 0.88 = 3,693 Wh, because the inverter loses 12% as heat and overhead.
Rated storage (Wh) = DC energy ÷ usable discharge. At 80% usable discharge the bank must store 3,693 ÷ 0.80 = 4,616 Wh, because only 80% of the stored energy is available to use.
Required capacity (Ah) = rated storage (Wh) ÷ bank voltage (V). At 24 V that is 4,616 ÷ 24 = 192.4 Ah. The workbench does all four steps at once and returns this amp-hour figure.
Worked example: a 650 W load for 5 hours on a 24 V bank
Take the workbench defaults: a 650 W AC load, 5 hours of backup, a 24 V DC bank, 88% inverter efficiency and 80% usable discharge. That is a small home backup or cabin case, and each step below uses those figures. Record these assumptions whenever you use Inverter Battery Calculator with another system. This is the uncertainty that a Inverter Battery Calculator worksheet should make visible.
| Step | Calculation | Result |
|---|---|---|
| AC energy needed | 650 W × 5 h | 3,250 Wh |
| DC energy after 88% efficiency | 3,250 ÷ 0.88 | 3,693 Wh |
| Rated storage after 80% usable discharge | 3,693 ÷ 0.80 | 4,616 Wh |
| Required capacity at 24 V | 4,616 ÷ 24 | 192.4 Ah |
| Required capacity at 48 V | 4,616 ÷ 48 | 96.2 Ah |
| DC current at 24 V | 650 ÷ 24 ÷ 0.88 | 30.8 A |
So the job needs about 192 Ah at 24 V, or about 96 Ah at 48 V. The same energy at double the voltage needs half the amp-hours, which is why larger inverter systems move to 48 V: the current halves, cables get thinner and losses fall.
The same steps size larger jobs. A 1,000 W inverter load running for 4 hours on a 48 V system with 90% efficiency and 80% usable discharge needs 1,000 × 4 ÷ (48 × 0.90 × 0.80) = 115.7 Ah, which rounds in practice to about 120 Ah at 48 V. A 2 kW load for the same 4 hours needs roughly 240 Ah at 48 V, and a 3 kW load running for 8 hours needs roughly 700 Ah at 48 V, which is a large bank and often easier to think of in kilowatt-hours: 33.3 kWh of rated storage.
Common inverter sizes at a glance
The table below applies 90% inverter efficiency and 80% usable discharge to the inverter sizes readers ask about most, at 48 V except for the last row, which repeats the worked example at 24 V. Rated storage is the energy the bank must hold before efficiency and usable-discharge limits are applied.
| Inverter load | Hours | AC energy | Rated storage | Required Ah |
|---|---|---|---|---|
| 1 kW (48 V) | 4 | 4,000 Wh | 5,556 Wh | 120 Ah |
| 2 kW (48 V) | 4 | 8,000 Wh | 11,111 Wh | 240 Ah |
| 3 kW (48 V) | 8 | 24,000 Wh | 33,333 Wh | 700 Ah |
| 5 kW (48 V) | 4 | 20,000 Wh | 27,778 Wh | 580 Ah |
| 650 W (24 V) | 5 | 3,250 Wh | 4,616 Wh | 192 Ah |
Two patterns are worth noting. Doubling the hours roughly doubles the bank, and doubling the load does the same, because the formula is linear in both. And the bank voltage matters as much as the load: the 650 W case needs 192 Ah at 24 V but only 96 Ah at 48 V for exactly the same backup, because amp-hours are energy divided by voltage.
What each input means
AC appliance load is the watts the inverter will actually run, not its maximum rating. If the inverter is rated for 3,000 W but the backup load is only 1,200 W, enter 1,200 W. Entering the inverter rating instead of the real load oversizes the bank and the budget with it.
Required operating hours is how long the backup must last, and it is usually the biggest factor in battery size. Doubling the hours roughly doubles the bank if everything else stays the same, so measure the real backup window rather than guessing it.
Nominal DC bank voltage is the battery bank voltage: 12 V, 24 V or 48 V in most systems. For the same power, a lower-voltage bank must deliver more amps, which makes cables thicker, increases losses and raises cost. Above about 2 kW of inverter size, a 48 V system is usually the safer and more practical choice. A second Inverter Battery Calculator scenario can reveal whether that difference matters. Use Inverter Battery Calculator to examine the numbers, not to override a manufacturer limit.
Inverter efficiency is the share of DC energy that reaches the AC load, 88% in the default case. The rest is lost as heat and inverter overhead. Use a measured figure when you have one; the default is a planning figure for a small inverter system.
Usable discharge is the share of the battery you plan to use, 80% in the default case. LiFePO4 banks are often sized around 80% usable discharge in practical backup calculations, while lead-acid systems are often limited to around 50% for longer life. The workbench applies the figure you enter, so a lead-acid bank sized at 80% will be undersized in real life.
Reading the result — and its limits
Treat the result as a planning estimate for a steady average load. Real loads vary: compressors cycle, motors draw a starting surge several times their running current, and inverters consume power even with no load. A design that meets the daily energy total can still fail on a brief peak, so check sustained current and short-duration limits against the battery and inverter datasheets separately.
Current is the reason voltage matters. A 2,000 W load draws about 166.7 A at 12 V before losses, about 83.3 A at 24 V and about 41.7 A at 48 V. That simple comparison shows why 48 V is often preferred once inverter systems get bigger: lower current means thinner cables, smaller fuses and less voltage drop.
Think in both amp-hours and kilowatt-hours. Amp-hours are useful for battery labelling, but kilowatt-hours are often the easier way to understand how much real backup energy a bank holds, especially when comparing banks at different voltages. The calculator cannot approve an installation: inverter voltage range, BMS current limits, cable size, fusing and ventilation must agree with the manufacturer's documentation.
Sources and verification status
Author: Saqib Jillani · Reviewer: lithiumbattery.info Editorial Team
The formulas and worked numbers on this page are arithmetic from the inputs stated beside them, and every figure can be reworked with a pocket calculator. The workbench returns required capacity in amp-hours only; the intermediate energy figures in the worked example are the same calculation shown step by step. The 88% efficiency and 80% usable-discharge defaults are planning figures, not measurements, and the 80% usable discharge for LiFePO4 against about 50% for lead-acid is the planning convention used across this site's battery guides. A named inverter efficiency source and a named battery datasheet citation are still to be added. For background on how batteries store energy, see the U.S. Department of Energy battery reference linked below. The result from Inverter Battery Calculator should be compared with the equipment specification. A follow-up using Inverter Battery Calculator should change only one input at a time.