What this calculator does
This calculator sizes a battery bank for an off-grid home, cabin or farm from daily energy use and the number of days the bank must last without charging. Enter the critical daily demand in kilowatt-hours, the sunless backup days, the delivery efficiency and the usable share of the battery. The workbench returns the stored energy the bank must hold, in kilowatt-hours.
Short answer: required stored energy equals daily demand times backup days divided by efficiency times usable fraction. A home using 5.6 kWh per day with 2 sunless days, 88% efficiency and 80% usable battery needs 5.6 × 2 ÷ (0.88 × 0.80) = 15.9 kWh of stored energy. The practical value of Off-Grid Battery Calculator depends on the accuracy of those inputs. A cautious interpretation of Off-Grid Battery Calculator includes the relevant operating limits.
The workbench answers in kilowatt-hours, not amp-hours, because daily loads, autonomy and battery-bank size are all easier to compare in energy units. To get amp-hours, multiply the kilowatt-hours by 1,000 and divide by the system voltage: 15.9 kWh at 48 V is 15,900 ÷ 48 = 331 Ah.
The formulas behind the result
Four formulas cover everything on this page. The first two are the planning steps; the last two convert the answer into the units battery labels use.
Load energy (kWh) = daily demand (kWh) × backup days. The default case is 5.6 × 2 = 11.2 kWh that the loads must receive over the backup period.
Required stored energy (kWh) = load energy ÷ efficiency ÷ usable fraction. The workbench does this step: 11.2 ÷ 0.88 ÷ 0.80 = 15.9 kWh. Efficiency covers inverter, cable and control losses; usable fraction covers the reserve that stays in the battery.
Required capacity (Ah) = stored energy (Wh) ÷ system voltage (V). At 48 V that is 15,900 ÷ 48 = 331 Ah, and at 24 V it is 15,900 ÷ 24 = 663 Ah.
Battery bank size in kilowatt-hours (nominal) = system voltage (V) × capacity (Ah) ÷ 1,000. A 48 V, 100 Ah battery stores 48 × 100 ÷ 1,000 = 4.8 kWh nominal, before efficiency and usable limits are applied.
Worked example: 5.6 kWh a day with 2 sunless days
Take the workbench defaults: a critical daily demand of 5.6 kWh, 2 sunless backup days, 88% delivery efficiency and an 80% usable battery fraction. That is a modest off-grid home, and each step below uses those figures. Record these assumptions whenever you use Off-Grid Battery Calculator with another system. This is the uncertainty that a Off-Grid Battery Calculator worksheet should make visible.
| Step | Calculation | Result |
|---|---|---|
| Load energy over 2 days | 5.6 kWh × 2 | 11.2 kWh |
| After 88% delivery efficiency | 11.2 ÷ 0.88 | 12.7 kWh |
| After 80% usable fraction | 12.7 ÷ 0.80 | 15.9 kWh |
| Required capacity at 48 V | 15,900 ÷ 48 | 331 Ah |
| Required capacity at 24 V | 15,900 ÷ 24 | 663 Ah |
| 48 V 100 Ah modules needed | 331 ÷ 100 | 4 modules |
So the home needs about 15.9 kWh of stored energy, which is 331 Ah at 48 V or four 48 V 100 Ah modules, with a little headroom. At 24 V the same energy needs 663 Ah, which is why most full-time off-grid homes use 48 V: the current halves and the wiring stays manageable.
A smaller case shows the same steps. A cabin using 4,000 Wh per day with 2 days of autonomy on a 48 V system at 80% usable discharge and 88% efficiency needs 4,000 × 2 ÷ 48 ÷ 0.88 ÷ 0.80 = 236.7 Ah. Without the efficiency step the same case gives 208.3 Ah, which is about 28 Ah short, so leaving efficiency out is not a rounding error.
In practice, many designers also add a reserve margin, because real systems are affected by inverter losses, weather changes, battery ageing and load growth. The workbench result is the minimum before that margin, not the final shopping list.
Common off-grid sizes at a glance
The table below applies the workbench defaults, 88% efficiency and 80% usable fraction, to the daily loads and autonomy periods readers ask about most. Stored energy is what the bank must hold; the last column converts it to amp-hours at 48 V.
| Daily load | Backup days | Stored energy | Capacity at 48 V |
|---|---|---|---|
| 2 kWh | 1 | 2.8 kWh | 59 Ah |
| 3 kWh | 1 | 4.3 kWh | 89 Ah |
| 4 kWh | 2 | 11.4 kWh | 237 Ah |
| 5.6 kWh | 2 | 15.9 kWh | 331 Ah |
| 8 kWh | 2 | 22.7 kWh | 474 Ah |
| 10 kWh | 3 | 42.6 kWh | 888 Ah |
The same loads in familiar bank sizes help with planning. A small cabin may work well with a 48 V 100 Ah battery, about 4.8 kWh nominal. A medium off-grid home often starts around 48 V 200 Ah, about 9.6 kWh nominal. A larger home with heavier daily use may need around 48 V 400 Ah, about 19.2 kWh nominal, and farms and high-demand properties may need around 48 V 600 Ah to 1,000 Ah, roughly 29 kWh to 48 kWh of nominal storage. Each of those nominal figures still needs the efficiency and usable-fraction steps applied before it can be compared with the table above.
What each input means
Critical daily demand is the total daily load in kilowatt-hours, and it is the foundation of the whole design. Add up lights, appliances, pumps, electronics and inverter-powered loads, using measured or realistic average consumption rather than nameplate watts. A fridge that draws 150 W while running but cycles on and off does not use 150 × 24 watt-hours a day.
Sunless backup days is how many days the bank must last without charging. One to three days is common for many off-grid systems, but remote and weather-sensitive sites may need more. Each extra day adds a full day of demand to the bank, so this input is usually the second-biggest factor after daily load. A second Off-Grid Battery Calculator scenario can reveal whether that difference matters. Use Off-Grid Battery Calculator to examine the numbers, not to override a manufacturer limit.
Delivery efficiency combines the losses between the battery and the load: inverter conversion, cables and control electronics. The 88% default is a planning figure for a small inverter system. If the system has long cable runs or a large inverter idling, expect a lower figure.
Usable battery fraction is the share of the battery you plan to use, 80% in the default case. LiFePO4 is often sized around 80% usable discharge in practical off-grid planning, while lead-acid usually needs a more conservative limit, nearer 50%, which means a much larger nominal bank for the same usable energy.
Reading the result — and its limits
Think in kilowatt-hours first, then convert to amp-hours at the chosen voltage. Kilowatt-hours make off-grid planning easier because daily loads, autonomy and battery-bank size are all energy numbers, while amp-hours only make sense once a voltage is fixed. A 100 Ah battery at 48 V and a 100 Ah battery at 24 V hold very different energy.
System voltage matters more as systems get larger. The same power draw that feels manageable at 48 V may become impractical at 12 V because the current is four times higher. Small cabins can still use 12 V or 24 V systems, but most full-time off-grid homes benefit from 48 V, especially with a larger inverter, pump loads or future expansion.
This calculator sizes storage, not charging. It does not work out how much solar is needed to recharge the bank, how many days of poor sun the panels must cover, or whether the inverter can start the largest load. Those need the solar sizing tools, and the result here should be checked against them. The calculator also cannot approve an installation: charger profile, BMS limits, fusing, wiring and ventilation must agree with the manufacturer's documentation.
Sources and verification status
Author: Saqib Jillani · Reviewer: lithiumbattery.info Editorial Team
The formulas and worked numbers on this page are arithmetic from the inputs stated beside them, and every figure can be reworked with a pocket calculator. The workbench returns required stored energy in kilowatt-hours only; the amp-hour conversions and module counts are hand calculations shown in this article. The 88% efficiency and 80% usable-fraction defaults are planning figures, not measurements, and the 80% usable discharge for LiFePO4 against about 50% for lead-acid is the planning convention used across this site's battery guides. The bank sizes quoted (48 V 100 Ah to 1,000 Ah) are common market sizes, not recommendations of specific products, and a named battery datasheet citation is still to be added. For background on how batteries store energy, see the U.S. Department of Energy battery reference linked below. The result from Off-Grid Battery Calculator should be compared with the equipment specification. A follow-up using Off-Grid Battery Calculator should change only one input at a time.