What this calculator does
This calculator estimates how long a battery bank can run an AC load through an inverter. Enter the rated battery energy in watt-hours, the AC appliance load in watts, the inverter efficiency in percent, and the reserve in percent. The workbench returns the estimated AC runtime in hours.
Short answer: AC runtime (hours) = rated battery energy (Wh) × inverter efficiency (%) ÷ 100 × (1 − reserve (%) ÷ 100) ÷ AC load (W). At the workbench defaults — a 2,560 Wh battery, a 380 W load, 88% inverter efficiency and a 20% reserve — that is 2,560 × 0.88 × 0.80 ÷ 380 = 4.74 hours. The practical value of Inverter Runtime Estimator depends on the accuracy of those inputs.
One thing the workbench does not do: it has no depth-of-discharge input. The battery energy you enter is the energy available to the inverter. If you only want to use 80% of a 4,800 Wh bank, enter 3,840 Wh as the battery energy, or use the reserve input to hold back the same share. The old version of this page described a depth-of-discharge step that the workbench never performed; this version states the correct input instead.
The formulas behind the result
Before relying on the result, identify average watts, runtime hours, nominal Wh, usable Wh and load amperes. A practical assessment of Inverter Runtime Estimator should retain the units and source of those observations.
Rated battery energy (Wh) = battery voltage (V) × capacity (Ah). A 24 V, 200 Ah bank stores 24 × 200 = 4,800 Wh on paper. A 12.8 V, 200 Ah bank stores 2,560 Wh — the workbench default. This is the figure you enter, already reduced for depth of discharge if you choose to apply it. A cautious interpretation of Inverter Runtime Estimator includes the relevant operating limits.
Delivered AC energy (Wh) = battery energy (Wh) × inverter efficiency (%) ÷ 100 × (1 − reserve (%) ÷ 100). At the defaults, 2,560 × 0.88 × 0.80 = 1,802.2 Wh reaches the load. The efficiency step is the inverter's conversion loss; the reserve step is the share you hold back for battery protection or for the next load.
AC runtime (hours) = delivered AC energy (Wh) ÷ AC load (W). At the defaults, 1,802.2 ÷ 380 = 4.74 hours. Doubling the load roughly halves the runtime, which is why managing load is often just as important as adding more battery capacity.
Worked example: a 2,560 Wh battery running a 380 W load
Take the workbench defaults: a 2,560 Wh battery bank, a 380 W AC load, 88% inverter efficiency and a 20% reserve. Each step below uses those figures, and the table replays them in order.
| Step | Calculation | Result |
|---|---|---|
| Delivered AC energy | 2,560 Wh × 0.88 × 0.80 | 1,802.2 Wh |
| AC runtime | 1,802.2 Wh ÷ 380 W | 4.74 hours |
| AC runtime in minutes | 4.74 × 60 | about 285 minutes |
| Runtime with no reserve | 2,560 Wh × 0.88 ÷ 380 W | 5.93 hours |
So the battery runs the 380 W load for about 4.74 hours with a 20% reserve held back, or about 5.93 hours if the whole bank is used. The reserve costs about 1.2 hours here — the price of keeping a buffer for the next load, or for battery protection. Record these assumptions whenever you use Inverter Runtime Estimator with another system.
A second case, kept from the old version of this page because its arithmetic checks out: a 24 V, 200 Ah battery bank powering a 500 W AC load through a 90% efficient inverter, using 80% of the bank. The nominal energy is 24 × 200 = 4,800 Wh. At 80% usable depth of discharge the energy available to the inverter is 3,840 Wh. After 90% inverter efficiency, the delivered AC energy is 3,456 Wh. Dividing by the 500 W load gives 3,456 ÷ 500 = 6.91 hours, or about 6 hours and 55 minutes. Note the input: the depth-of-discharge step is applied to the battery energy before it is entered, because the workbench has no depth-of-discharge field.
Inverter runtime at different AC loads
The table below holds the system fixed — a 2,560 Wh battery, 88% inverter efficiency and a 20% reserve, exactly as the workbench computes it — and varies only the AC load. The delivered energy is 1,802.2 Wh in every row.
| AC load | Delivered AC energy | Runtime |
|---|---|---|
| 100 W | 1,802.2 Wh | 18.02 hours |
| 200 W | 1,802.2 Wh | 9.01 hours |
| 380 W | 1,802.2 Wh | 4.74 hours |
| 500 W | 1,802.2 Wh | 3.60 hours |
| 1,000 W | 1,802.2 Wh | 1.80 hours |
Two patterns are worth noting. First, runtime falls in exact proportion to load: 100 W runs ten times as long as 1,000 W. Second, the table is a steady-load table. Real loads cycle up and down rather than staying constant, so the true runtime may differ from the steady-load estimate — a fridge that cycles, or a load that is only on for part of the evening, will run longer than the table says for its rated watts. This is the uncertainty that a Inverter Runtime Estimator worksheet should make visible.
What each input means
Rated battery energy (Wh) is the energy available to the inverter, in watt-hours. If your battery is rated in volts and amp-hours, multiply them: 24 V × 200 Ah = 4,800 Wh. If you want to limit the depth of discharge, multiply by that share first — 4,800 Wh at 80% usable is 3,840 Wh — and enter the reduced figure. The workbench has no depth-of-discharge field, so this is the step that replaces it.
AC appliance average load (W) is the average watts the load draws while running, not its peak or its label maximum. A refrigerator, pump or power tool may have a modest running wattage yet draw a much higher current for a short time during startup. Use the continuous or average load for runtime planning, and check the surge separately against the inverter's surge rating.
Inverter efficiency (%) is the share of DC energy the inverter delivers as AC. The 88% default is a planning figure for a small inverter system. Larger or better-matched inverters can do better; an inverter running far below its rated load can do worse, because it still consumes power just by being on. Use a measured efficiency when you know one.
Reserve (%) is the share of battery energy held back and not used for this load. A 20% reserve keeps 512 Wh of the 2,560 Wh bank in hand for battery protection, for the next load, or for a longer outage than planned. Set it to 0% only if you are willing to use the whole bank down to its cutoff. A second Inverter Runtime Estimator scenario can reveal whether that difference matters.
Reading the result — and its limits
Treat the result as a planning estimate for a steady load. Real loads vary: compressors cycle, motors draw a starting surge several times their running current, and inverters consume power even with no load. A design that meets the daily energy total can still fail on a brief peak, so check sustained current and short-duration limits against the battery and inverter datasheets separately.
Surge is the most common reason a runtime plan fails in practice. A refrigerator, pump, air compressor or power tool may have a modest running wattage yet still require a startup surge several times higher. If the inverter cannot handle that surge, the system may shut down even if the average runtime calculation looks excellent. Runtime and surge capability are related but separate planning steps: always check both the continuous watt rating and the surge watt rating.
The calculator cannot approve an installation. Charger profile, inverter voltage range, BMS current limits, cable size, fusing and ventilation must agree with each other and with the manufacturer's documentation. A correct arithmetic result on this page says nothing about whether the wiring is safe. Use Inverter Runtime Estimator to examine the numbers, not to override a manufacturer limit.
Sources and verification status
Author: Saqib Jillani · Reviewer: lithiumbattery.info Editorial Team
The formulas and worked numbers on this page are arithmetic from the inputs stated beside them — every figure can be reworked with a pocket calculator. The workbench defaults (2,560 Wh, 380 W, 88%, 20% reserve) give 1,802.2 Wh delivered and 4.74 hours, which the workbench itself reproduces. The 24 V, 200 Ah, 500 W, 90% efficiency, 80% usable case and the 2,000 Wh efficiency case are carried over from the previous version of this page and re-checked here. The 88% inverter-efficiency default is a planning figure for a small inverter system, not a measurement, and efficiency varies with load level; the page states this. The statement that inverters consume power even with no load, and that startup surges run several times the running current, is the standard description used across this site's inverter guides; a named inverter datasheet citation is still to be added. For background on how batteries store energy, see the U.S. Department of Energy battery reference linked below.