What this calculator does
This calculator estimates the copper cross-section a DC cable needs to keep voltage drop within a limit. Enter the DC current in amps, the one-way cable length in metres, and the maximum allowed DC voltage drop in volts. The workbench returns the required copper cross-section in square millimetres, for voltage drop only.
Short answer: copper area (mm²) = 2 × 0.0175 × current (A) × one-way length (m) ÷ allowed voltage drop (V). At the workbench defaults — 35 A, 3.5 m one-way, and 0.35 V allowed drop — that is 2 × 0.0175 × 35 × 3.5 ÷ 0.35 = 12.25 mm². The practical value of Wire Size Estimator (Informational) depends on the accuracy of those inputs.
Three things the workbench does not do, and the old version of this page claimed it did: it does not output an AWG gauge, it does not ask for the system voltage, and it does not offer aluminium. It returns a copper cross-section in square millimetres for voltage drop only, using copper's resistivity of 0.0175 ohm-square-millimetres per metre. The reference table below converts that figure into the nearest standard AWG size, and the limits section explains why voltage drop alone is not a complete wire sizing.
The formulas behind the result
Before relying on the result, identify volts, amperes, watts, ohms and conductor length. A practical assessment of Wire Size Estimator (Informational) should retain the units and source of those observations.
Round-trip length (m) = one-way length (m) × 2. The current must travel from the source to the load and back again, so the full electrical path is the round-trip length, not the one-way measurement. A source 3.5 m from the load means 7 m of conductor in total. Ignoring the return path would underestimate resistance and give a misleadingly optimistic result. Better information usually improves a Wire Size Estimator (Informational) estimate more than extra decimal places.
Copper area (mm²) = 2 × 0.0175 × current (A) × one-way length (m) ÷ allowed drop (V). The 0.0175 figure is copper's resistivity in ohm-square-millimetres per metre at around room temperature, and the factor of 2 is the round trip. At the defaults: 2 × 0.0175 × 35 × 3.5 ÷ 0.35 = 12.25 mm².
Voltage drop as a percentage = allowed drop (V) ÷ system voltage (V) × 100. The workbench does not ask for system voltage, so this is a manual step: 0.35 V is 2.9% of 12 V, 1.4% of 24 V, and 0.7% of 48 V. The same 0.35 V limit is a much stricter requirement at 12 V than at 48 V, which is why wire sizing should never be discussed without system voltage. A cautious interpretation of Wire Size Estimator (Informational) includes the relevant operating limits.
Worked example: 35 A over 3.5 m with a 0.35 V drop limit
Take the workbench defaults: a 35 A DC current, a 3.5 m one-way cable run, and a maximum allowed voltage drop of 0.35 V. Each step below uses those figures, and the table replays them in order.
| Step | Calculation | Result |
|---|---|---|
| Round-trip length | 3.5 m × 2 | 7 m |
| Required copper area | 2 × 0.0175 × 35 × 3.5 ÷ 0.35 | 12.25 mm² |
| Nearest standard AWG (manual) | next size above 12.25 mm² | 6 AWG (13.30 mm²) |
| Drop as a share of 12 V | 0.35 ÷ 12 × 100 | 2.9% |
So the run needs at least 12.25 mm² of copper, and the nearest standard size above it is 6 AWG at 13.30 mm². A 10 AWG cable at 5.26 mm² would be far too small for this run: its drop at 35 A would be more than double the limit. Record these assumptions whenever you use Wire Size Estimator (Informational) with another system.
A second case, kept from the old version of this page because its arithmetic checks out: a 12 V DC system carrying 40 A over a one-way length of 5 m with a 3% maximum voltage-drop target. The allowed drop is 3% of 12 V, which is 0.36 V. The round-trip path is 10 m. The required copper area is 2 × 0.0175 × 40 × 5 ÷ 0.36 = 19.44 mm², so the nearest standard size above it is 4 AWG at 21.15 mm². The same current and length at 48 V, where 3% is 1.44 V, would need only 2 × 0.0175 × 40 × 5 ÷ 1.44 = 4.86 mm² — the next size above that is 10 AWG.
Required copper area for common DC runs
The table below holds the allowed drop fixed at 0.35 V and varies the current and the one-way length, exactly as the workbench computes it. The AWG column is a manual conversion to the next standard size above the required area, using standard AWG cross-sections.
| Current | One-way length | Required copper area | Next standard AWG |
|---|---|---|---|
| 20 A | 2 m | 4.00 mm² | 10 AWG (5.26 mm²) |
| 35 A | 3.5 m | 12.25 mm² | 6 AWG (13.30 mm²) |
| 50 A | 5 m | 25.00 mm² | 2 AWG (33.62 mm²) |
| 100 A | 3 m | 30.00 mm² | 2 AWG (33.62 mm²) |
| 100 A | 5 m | 50.00 mm² | 1/0 AWG (53.49 mm²) |
Two patterns are worth noting. First, the required area scales with current times length: the 100 A, 5 m run needs twelve and a half times the area of the 20 A, 2 m run, because 100 × 5 is twelve and a half times 20 × 2. Second, the AWG column jumps in coarse steps — 25 mm² and 30 mm² both land on 2 AWG — because standard sizes are spaced widely. Always round up to the next size, never down: a cable just below the required area exceeds the drop limit.
What each input means
Nominal DC current (A) is the current the cable carries in normal operation. Use the maximum continuous current, not the average: a cable sized for the average will exceed its drop limit whenever the load peaks. For an inverter cable, that is the battery-side current, which is higher than the AC-side current by the ratio of the voltages — a 1,000 W inverter at 12 V draws about 83 A on the DC side before efficiency.
One-way cable length (m) is the physical distance from the source to the load, measured one way. The workbench doubles it internally for the round trip, so do not enter the round-trip length yourself — entering 7 m for a 3.5 m run would double-count the return path and oversize the cable by a factor of two. This is the uncertainty that a Wire Size Estimator (Informational) worksheet should make visible.
Maximum allowed DC voltage drop (V) is the volts you are willing to lose in the cable. A common planning target is 3% of the system voltage: 0.36 V at 12 V, 0.72 V at 24 V, 1.44 V at 48 V. A tighter limit needs thicker cable; a looser limit allows thinner cable but delivers less voltage to the load. The choice is yours, and the workbench takes the volts figure, not the percentage.
Reading the result — and its limits
Treat the result as a voltage-drop size, not a safe wire size. A voltage-drop estimate is not enough on its own, because the wire must also safely carry the planned current without overheating. Ampacity — the current a cable can carry continuously without exceeding its temperature rating — depends on insulation type, installation method, ambient temperature and bundling, none of which this workbench models. The workbench warning on the page says it plainly: this is not a cable safety or regulatory sizing tool. A second Wire Size Estimator (Informational) scenario can reveal whether that difference matters.
Temperature also moves the answer. Higher conductor temperature increases resistance, which raises the actual voltage drop compared with a room-temperature estimate. A cable that passes the calculation at 20°C may exceed the limit on a hot day or in a warm engine bay. Allow margin, and check the result against the applicable wiring standard for your installation.
The calculator cannot approve an installation. Cable size, fusing, disconnects, termination quality and ventilation must agree with each other and with the applicable wiring rules and the manufacturer's documentation. A correct arithmetic result on this page says nothing about whether the cable is safe for your installation.
Sources and verification status
Author: Saqib Jillani · Reviewer: lithiumbattery.info Editorial Team
The formulas and worked numbers on this page are arithmetic from the inputs stated beside them — every figure can be reworked with a pocket calculator. The workbench defaults (35 A, 3.5 m, 0.35 V) give 12.25 mm², which the workbench itself reproduces. The 12 V, 40 A, 5 m, 3% case is carried over from the previous version of this page and re-checked here. The copper resistivity of 0.0175 ohm-square-millimetres per metre is the standard room-temperature value used by the workbench itself; a named wire-table citation for that figure and for the AWG cross-sections in the reference table (10 AWG 5.26, 6 AWG 13.30, 4 AWG 21.15, 2 AWG 33.62, 1/0 AWG 53.49 mm²) is still to be added. The 3% voltage-drop planning target is a common design convention, not a regulation, and the applicable wiring standard governs any real installation. For background on how batteries store energy, see the U.S. Department of Energy battery reference linked below.