What this calculator does
This calculator works out how much battery capacity a solar array's surplus production needs. Enter the solar array's rated power, the effective peak sun hours, the energy used directly during the day, and the storage bank's nominal voltage, and the workbench returns the battery capacity in amp-hours for the surplus alone. It answers one half of solar sizing: what to do with the energy the panels produce that the house does not use immediately.
Short answer: surplus amp-hours = (array watts × peak sun hours − daytime use) ÷ bank volts. The workbench defaults are 1,200 W, 4 peak sun hours, 1,500 Wh of daytime use and a 24 V bank, giving (1,200 × 4 − 1,500) ÷ 24 = 137.5 Ah. The practical value of Solar Panel Battery Size Calculator depends on the accuracy of those inputs. A cautious interpretation of Solar Panel Battery Size Calculator includes the relevant operating limits.
Keep the two halves of solar sizing apart. This workbench sizes storage for production surplus. Sizing storage for the household load — how much energy the home needs overnight or through cloudy days — is a different calculation, covered below, and the workbench does not do it. A complete system needs both.
The formulas behind the result
Three formulas cover the page: the workbench formula, the solar-yield formula behind it, and the load-based sizing formula for the other half of the job.
Surplus capacity (Ah) = max(0, PV watts × peak sun hours − daytime loads in Wh) ÷ bank volts. Daily production minus daytime use is the surplus energy; dividing by volts turns it into amp-hours at the bank voltage. If daytime use exceeds production, the surplus is zero, not negative — there is nothing to store.
Simplified daily yield (Wh) = array watts × peak sun hours × planning efficiency. With 3,000 W of PV, 5 peak sun hours and an 80% planning efficiency, the simplified yield is 12,000 Wh per day. With 800 W, 5 peak sun hours and 78% efficiency it is about 3,120 Wh per day. Peak sun hours are not daylight hours: they are the equivalent hours at full rated power.
Load-based nominal storage (Wh) = daily load Wh × autonomy days × (1 + reserve) ÷ load-path efficiency ÷ depth of discharge. This is the manual step for the load half: a 5 kWh daily load at 80% depth of discharge and 92% delivery efficiency needs about 6.79 kWh nominal before any extra reserve. A 5 kW array is a power rating, while a 5 kWh battery is an energy rating — the two numbers describe different things.
The workbench result carries no efficiency, depth-of-discharge or reserve allowance. It is the raw surplus capacity; usable storage sizing also requires charging and conversion efficiency, safety headroom, weather and controller limits, as the workbench itself notes.
Worked example: a 1,200 W array with 4 peak sun hours
Take the workbench as it loads: a 1,200 W array, 4 effective peak sun hours, 1,500 Wh used directly during the day, and a 24 V storage bank. The steps below replay the default case, then the load-based sizing case for a 5,000 Wh-per-day home. Record these assumptions whenever you use Solar Panel Battery Size Calculator with another system. This is the uncertainty that a Solar Panel Battery Size Calculator worksheet should make visible.
| Step | Calculation | Result |
|---|---|---|
| Daily production | 1,200 W × 4 h | 4,800 Wh |
| Surplus after daytime use | 4,800 − 1,500 | 3,300 Wh |
| Surplus capacity at 24 V | 3,300 ÷ 24 | 137.5 Ah |
| Load case: energy needed | 5,000 × 1.25 × 1.10 | 6,875 Wh |
| Load case: after 92% efficiency | 6,875 ÷ 0.92 | 7,473 Wh |
| Load case: nominal at 80% DoD | 7,473 ÷ 0.80 | 9,341 Wh |
| Load case: amp-hours at 48 V | 9,341 ÷ 48 | 194.6 Ah |
The load case uses 5,000 Wh per day of selected critical loads, 1.25 days of autonomy, a 10% reserve, 92% load-path efficiency, 80% depth of discharge and a 48 V bank. Its answer, about 9.34 kWh or 194.6 Ah, is much larger than the 137.5 Ah surplus figure — because the two calculations answer different questions. The surplus figure stores one day's excess production; the load figure keeps the home running through the night and into the next day.
Two more load cases show the range. With 1,800 Wh per day, one day of autonomy, 85% depth of discharge, 90% load-path efficiency and a 10% reserve, the nominal target is about 2.59 kWh — roughly 215.7 Ah at 12 V or 107.8 Ah at 24 V. With 8,000 Wh per day, two days of autonomy, 80% depth of discharge, 92% efficiency and a 15% reserve, the target is about 25 kWh, or roughly 520.8 Ah at 48 V.
Surplus capacity for common array sizes
The table below applies the workbench formula to four common array sizes, all at 4 peak sun hours and 1,500 Wh of daytime use, with no efficiency or depth-of-discharge allowance. Every cell is (array watts × 4 − 1,500) ÷ bank volts.
| Array | Daily production | Surplus energy | At 24 V | At 48 V |
|---|---|---|---|---|
| 800 W | 3,200 Wh | 1,700 Wh | 70.8 Ah | 35.4 Ah |
| 1,200 W | 4,800 Wh | 3,300 Wh | 137.5 Ah | 68.8 Ah |
| 2,000 W | 8,000 Wh | 6,500 Wh | 270.8 Ah | 135.4 Ah |
| 3,000 W | 12,000 Wh | 10,500 Wh | 437.5 Ah | 218.8 Ah |
Two patterns are worth noting. Surplus capacity grows faster than array size, because daytime use is fixed: doubling the array from 800 W to 1,600 W more than doubles the surplus. And a 48 V bank needs half the amp-hours of a 24 V bank for the same surplus energy — the energy is identical, only the rating changes.
What each input means
Solar array rated power is the array's nameplate DC power, in watts. A 3 kW array does not automatically require a fixed battery kilowatt-hour value: the same array serves very different batteries depending on daytime use, autonomy needs and backup priorities. Two homes can share a 5 kW array and need very different batteries.
Effective peak sun hours are the equivalent hours per day at full rated power, not the hours of daylight. Four peak sun hours on a 1,200 W array means 4,800 Wh before losses, regardless of whether the sun shone for eight weaker hours. Use a local solar figure for your site and season, not a yearly average, when the number decides a purchase.
Direct daytime use is the energy the home consumes while the sun is producing, in watt-hours. Energy used directly never reaches the battery, so it is subtracted before sizing storage. For cycling equipment, use realistic average energy rather than maximum wattage for 24 hours. A second Solar Panel Battery Size Calculator scenario can reveal whether that difference matters. Use Solar Panel Battery Size Calculator to examine the numbers, not to override a manufacturer limit.
Storage bank nominal voltage is the rated voltage of the battery bank, in volts — 12 V, 24 V or 48 V in most homes. The same surplus energy needs half the amp-hours at 48 V as at 24 V, which is why larger systems use higher-voltage banks.
Reading the result — and its limits
Treat the result as the raw surplus capacity, not a battery to buy. Add headroom for charging and conversion efficiency, a usable depth-of-discharge window, weather and controller limits before choosing a bank. A 10 kWh nominal battery at 80% planned depth of discharge offers 8 kWh of planned discharge energy before delivery losses, and if the load path is 92% efficient the loads receive about 7.36 kWh from that window.
The result also says nothing about the hourly shape of production. A 5 kW array with 4 peak sun hours and 75% planning efficiency produces a simplified 15 kWh per day, which is more than an 8 kWh daily load — but only 7 kWh per day remains on an average day to recover a discharged battery, and a cloudy week still needs autonomy the surplus figure cannot provide. Size for the worst stretch, not the average day.
A final check: compare the surplus amp-hours with the load-based figure before ordering. If the surplus figure is much larger than the load figure, the battery will sit partly unused; if it is much smaller, the home will still need grid or generator support on cloudy stretches.
Finally, the workbench cannot approve a system. Charger profile, charge-controller voltage range, BMS current limits, cable size, fusing and ventilation must agree with each other and with the manufacturer's documentation. A correct arithmetic result says nothing about whether the wiring is safe.
Sources and verification status
Author: Saqib Jillani · Reviewer: lithiumbattery.info Editorial Team
The formulas and worked numbers on this page are arithmetic from the inputs stated beside them — every figure can be reworked with a pocket calculator. The load-case figures (5,000 Wh per day at 1.25 days autonomy, 1,800 Wh at one day, 8,000 Wh at two days) are carried over from the previous version of this page with their assumptions stated beside them. The planning efficiencies (92% load path, 78–80% solar yield) are planning figures, not measurements, and the page labels them as such. For background on how batteries store energy, see the U.S. Department of Energy battery reference linked below. The result from Solar Panel Battery Size Calculator should be compared with the equipment specification. A follow-up using Solar Panel Battery Size Calculator should change only one input at a time.