What this calculator does
This calculator converts a battery's amp-hour rating into the energy it stores, in kilowatt-hours. Enter the capacity in amp-hours and the nominal voltage, and the workbench returns kilowatt-hours, with the watt-hour figure shown alongside. The conversion is the one that lets you compare batteries honestly, because amp-hours alone mean nothing without voltage.
Short answer: kilowatt-hours = amp-hours × volts ÷ 1,000. A 100 Ah battery at 12 V stores 100 × 12 ÷ 1,000 = 1.2 kWh, while a 100 Ah battery at 48 V stores 100 × 48 ÷ 1,000 = 4.8 kWh. Same amp-hours, four times the energy. A cautious interpretation of Ah to kWh Calculator includes the relevant operating limits.
The workbench defaults show the conversion at its most familiar: 100 Ah at 12.8 V is 1,280 Wh, or 1.28 kWh — the common 12 V LiFePO4 battery. If that figure feels small beside a household load measured in kilowatt-hours, that is the point: a single 12 V battery is a small amount of energy, and a home needs several of them. The practical value of Ah to kWh Calculator depends on the accuracy of those inputs.
That is why comparing batteries by amp-hours alone misleads. A 100 Ah, 12 V battery and a 100 Ah, 48 V battery share a rating and share nothing else: one holds 1.2 kWh, the other 4.8 kWh. Energy, not amp-hours, is what runs your loads.
The formulas behind the result
Two steps cover the whole conversion. All voltages here are nominal pack voltages — 12 V, 12.8 V, 24 V, 48 V or 51.2 V — not full-charge voltages.
Step 1: amp-hours to watt-hours. Wh = Ah × V. The workbench defaults are 100 Ah and 12.8 V, giving 100 × 12.8 = 1,280 Wh, which the workbench shows as its secondary result.
Step 2: watt-hours to kilowatt-hours. kWh = Wh ÷ 1,000. So 1,280 Wh is 1.28 kWh, the workbench's main result for the defaults.
Combined: kWh = Ah × V ÷ 1,000. A 200 Ah battery at 48 V stores 200 × 48 ÷ 1,000 = 9.6 kWh. A 300 Ah bank at 48 V stores 300 × 48 ÷ 1,000 = 14.4 kWh. Run it backwards to check: kilowatt-hours × 1,000 ÷ volts must return the amp-hours you started with.
A quick sense check: a kilowatt-hour is 1,000 watt-hours, so any result below 1 kWh is a fraction of a unit of household energy. A 100 Ah, 12 V battery at 1.2 kWh runs a 100 W load for about 12 hours before losses; a 300 Ah, 48 V bank at 14.4 kWh runs the same load for about six days. The arithmetic is the same in both cases — only the inputs change. This is the uncertainty that a Ah to kWh Calculator worksheet should make visible.
Usable energy is a separate step the workbench does not take. A 300 Ah, 48 V bank holds 14.4 kWh nominal; at a 90% depth-of-discharge target the usable DC energy is about 12.96 kWh before inverter losses, and at 90% inverter efficiency the usable AC energy is lower still. A battery listed as 9.6 kWh may not deliver the full 9.6 kWh to AC loads. Record these assumptions whenever you use Ah to kWh Calculator with another system.
Worked example: 100 Ah at 12.8 V
Take the workbench as it loads: a 100 Ah battery at 12.8 V nominal. The steps below replay the default case, then the same capacity at the other common system voltages.
| Step | Calculation | Result |
|---|---|---|
| Energy in watt-hours | 100 Ah × 12.8 V | 1,280 Wh |
| Energy in kilowatt-hours | 1,280 ÷ 1,000 | 1.28 kWh |
| Same capacity at 12 V | 100 × 12 ÷ 1,000 | 1.2 kWh |
| Same capacity at 48 V | 100 × 48 ÷ 1,000 | 4.8 kWh |
| 200 Ah at 48 V | 200 × 48 ÷ 1,000 | 9.6 kWh |
| 300 Ah at 48 V, 90% usable | 14.4 × 0.90 | 12.96 kWh |
The third and fourth rows are the warning. One hundred amp-hours is 1.2 kWh at 12 V and 4.8 kWh at 48 V, so a shopper who compares amp-hours across voltages is comparing different amounts of energy. Always convert to kilowatt-hours before deciding which battery is bigger.
A daily-load example: if your appliances use 5 kWh per day, a 200 Ah, 48 V bank storing about 9.6 kWh nominal covers more than one day before losses and reserves. If your daily load is 10 kWh, the same bank may not cover a full day once inverter losses and depth-of-discharge limits are included.
Amp-hours to kilowatt-hours at the common voltages
The table below converts five common capacities at four common system voltages. Every cell is amp-hours × volts ÷ 1,000, so any figure can be checked by hand. Common lithium capacities are 50 Ah, 100 Ah, 200 Ah, 280 Ah and 300 Ah; 51.2 V is the usual nominal voltage for a LiFePO4 server-rack battery.
| Capacity | 12 V | 24 V | 48 V | 51.2 V |
|---|---|---|---|---|
| 50 Ah | 0.6 kWh | 1.2 kWh | 2.4 kWh | 2.56 kWh |
| 100 Ah | 1.2 kWh | 2.4 kWh | 4.8 kWh | 5.12 kWh |
| 200 Ah | 2.4 kWh | 4.8 kWh | 9.6 kWh | 10.24 kWh |
| 280 Ah | 3.36 kWh | 6.72 kWh | 13.44 kWh | 14.34 kWh |
| 300 Ah | 3.6 kWh | 7.2 kWh | 14.4 kWh | 15.36 kWh |
Two patterns are worth noting. Doubling the voltage doubles the energy at the same amp-hours, and a 100 Ah, 51.2 V LiFePO4 battery — about 5.12 kWh — is why many 48 V-class server-rack batteries are advertised as approximately 5 kWh modules. Neither pattern changes the amp-hours; only the energy changes.
What each input means
Battery capacity in amp-hours is the charge the battery is rated to deliver, in Ah. A battery rated at 100 Ah can theoretically deliver 100 amps for one hour, 10 amps for 10 hours, or 5 amps for 20 hours under ideal conditions. Real delivery depends on discharge rate, temperature and age, so treat the rating as a reference condition, not a guarantee. Use Ah to kWh Calculator to examine the numbers, not to override a manufacturer limit.
Nominal voltage is the rated voltage of the battery or bank, in volts. Small systems may use 12 V, medium systems 24 V, and larger inverter systems 48 V or 51.2 V; smaller packs may be 12.8 V or 25.6 V nominal. Four 12 V, 100 Ah batteries in series become a 48 V, 100 Ah bank storing 4.8 kWh; the same four in parallel become a 12 V, 400 Ah bank storing the same 4.8 kWh. Wiring changes volts and amp-hours in opposite directions and leaves energy unchanged. A second Ah to kWh Calculator scenario can reveal whether that difference matters.
Capacity figures on a label are measured under the manufacturer's stated conditions, usually a stated discharge rate and temperature. A battery discharged much faster than its rating, or in the cold, delivers less than its rated amp-hours. The workbench cannot know those conditions, so its kilowatt-hours are the rated figure, not a measured one.
The workbench has no depth-of-discharge or efficiency input, and its answer is nominal energy. A 5 kW inverter is not the same as a 5 kWh battery — one is power, the other energy — and the kilowatt-hours here describe storage, not how fast it can be delivered.
Reading the result — and its limits
Treat the result as nominal stored energy, not delivered energy. A battery listed as 9.6 kWh may not deliver the full 9.6 kWh to AC loads after depth-of-discharge limits, inverter losses and reserve settings. A 10 kWh nominal bank at 90% usable depth of discharge provides about 9 kWh of usable DC energy, and at 90% inverter efficiency the usable AC energy is around 8.1 kWh.
The result also assumes the voltage you entered stays fixed. Real battery voltage sags under load and rises while charging, so the energy delivered over a full discharge differs slightly from the nominal multiplication. For sizing that is a second-order effect; for a precise energy audit, measure watt-hours directly.
When the result surprises you, check the voltage first. Entering 12 V for a 12.8 V battery understates the energy by about 6%: 100 × 12 ÷ 1,000 = 1.2 kWh against the correct 1.28 kWh. Entering the full-charge voltage of 14.6 V overstates it the other way. Nominal voltage is the figure the label and the datasheet agree on.
Finally, use kilowatt-hours for the decision and amp-hours for the shopping. Once you know the energy you need, convert back to amp-hours at your system voltage to pick a module — and confirm the module's series and parallel rules with the manufacturer before ordering. A follow-up using Ah to kWh Calculator should change only one input at a time.
Sources and verification status
Author: Saqib Jillani · Reviewer: lithiumbattery.info Editorial Team The result from Ah to kWh Calculator should be compared with the equipment specification.
The formulas and worked numbers on this page are arithmetic from the inputs stated beside them — every figure can be reworked with a pocket calculator. The series and parallel examples (four 12 V, 100 Ah batteries = 4.8 kWh either way) follow from the same formula. The 90% usable depth-of-discharge and 90% inverter-efficiency figures are planning conventions carried over from this site's sizing guides, not measurements, and the page labels them as such. For background on how batteries store energy, see the U.S. Department of Energy battery reference linked below.