What this calculator does
This calculator converts stored energy in watt-hours into the amp-hour rating a battery needs at your system voltage. Enter the energy in watt-hours and the nominal voltage, and the workbench returns the capacity in amp-hours.
Short answer: amp-hours = watt-hours ÷ volts. A 1,200 Wh target is 1,200 ÷ 12 = 100 Ah at 12 V, 50 Ah at 24 V and 25 Ah at 48 V. The energy is the same in all three cases — only the voltage changes, and the amp-hours change with it.
The conversion is the step between an energy plan and a battery purchase. Load studies, appliance lists, solar calculators and electricity bills all speak in watt-hours or kilowatt-hours, but battery listings speak in amp-hours. This page translates the first into the second, at the voltage you will actually build. The practical value of Wh to Ah Calculator depends on the accuracy of those inputs.
The formulas behind the result
One formula does the work: Ah = Wh ÷ V. The workbench defaults are 1,250 Wh and 12.8 V, giving 1,250 ÷ 12.8 = 97.7 Ah. The same 1,250 Wh at 24 V would be about 52 Ah, and at 48 V about 26 Ah — the higher the voltage, the fewer amp-hours the same energy needs.
The reverse formula is Wh = Ah × V, which is what the Ah-to-Wh calculator computes. The two pages are inverses of each other: converting 1,200 Wh at 12 V gives 100 Ah, and converting 100 Ah at 12 V back gives 1,200 Wh. If a round trip does not return the starting number, one of the two voltages was entered differently. A cautious interpretation of Wh to Ah Calculator includes the relevant operating limits.
Nominal capacity is only the first step. If you need 2,400 Wh of usable energy from a lithium battery and plan to use only 80 percent of its capacity, the nominal target becomes 2,400 ÷ 0.80 = 3,000 Wh, which at 24 V is 125 Ah. If an inverter is involved at 90 percent efficiency, the battery energy rises further — a 1,000 Wh AC load needs about 1,000 ÷ 0.90 = 1,111 Wh from the battery.
Combine the two adjustments and the target grows quickly. That same 1,000 Wh AC load, limited to 80 percent depth of discharge, needs 1,111 ÷ 0.80 = 1,388.75 Wh nominal, which at 12 V is about 115.7 Ah. The simple Wh-to-Ah conversion is the first step, not the final engineering design.
Worked example: a 4,800 Wh storage target at 12, 24 and 48 V
Take a 4,800 Wh nominal storage target — a common size for a small solar and backup system — and convert it at the three standard system voltages. The table replays the workbench formula at each voltage, then adds the usable-energy adjustment for a 2,400 Wh usable requirement.
| Step | Calculation | Result |
|---|---|---|
| 4,800 Wh at 12 V | 4,800 ÷ 12 | 400 Ah |
| 4,800 Wh at 24 V | 4,800 ÷ 24 | 200 Ah |
| 4,800 Wh at 48 V | 4,800 ÷ 48 | 100 Ah |
| 2,400 Wh usable at 80% DoD | 2,400 ÷ 0.80 | 3,000 Wh nominal |
| 3,000 Wh nominal at 24 V | 3,000 ÷ 24 | 125 Ah |
The first three rows show the core lesson: the same energy needs 400 Ah at 12 V but only 100 Ah at 48 V. A high-power inverter on a 12 V bank draws far more current than the same inverter on a 48 V bank, which is one reason larger solar and inverter systems are commonly built at 48 V or 51.2 V.
The daily-load version of the same calculation uses the loads from the old page. A 100 W refrigerator running the equivalent of 10 hours per day uses about 1,000 Wh; a 50 W fan for 8 hours uses 400 Wh; a 20 W lighting load for 5 hours uses 100 Wh. Together they need 1,500 Wh per day before losses, which at 24 V is 1,500 ÷ 24 = 62.5 Ah nominal per day of autonomy. Record these assumptions whenever you use Wh to Ah Calculator with another system.
A larger RV example from the old page also checks out. A 5,000 Wh daily need requires about 416.7 Ah at 12 V, 208.3 Ah at 24 V or 104.2 Ah at 48 V before adjustments — 5,000 ÷ 12 = 416.7, and the other two follow the same division. At 12 V the bank becomes impractically large, which is the point the numbers are making.
Common Wh to Ah conversions at a glance
The table below converts the energy targets readers ask about most, at 12, 24 and 48 V. Voltages are system class voltages; if your battery is a 51.2 V LiFePO4 pack, entering 51.2 V gives a more accurate result than entering 48 V — for example, 5,120 Wh ÷ 51.2 V = 100 Ah. This is the uncertainty that a Wh to Ah Calculator worksheet should make visible.
| Energy target | At 12 V | At 24 V | At 48 V |
|---|---|---|---|
| 1,200 Wh | 100 Ah | 50 Ah | 25 Ah |
| 2,400 Wh | 200 Ah | 100 Ah | 50 Ah |
| 4,800 Wh | 400 Ah | 200 Ah | 100 Ah |
| 5,000 Wh | 416.7 Ah | 208.3 Ah | 104.2 Ah |
| 10,000 Wh | 833.3 Ah | 416.7 Ah | 208.3 Ah |
The 10,000 Wh row is the one that usually settles the voltage choice. At 12 V the same energy needs about 833 Ah — a very large, high-current bank — while at 48 V it needs about 208 Ah. A 10 kWh target is common in larger solar and backup systems, and it is rarely built at 12 V.
The 5,000 Wh row shows the same pattern at a smaller scale: 416.7 Ah at 12 V against 104.2 Ah at 48 V. When the amp-hour figure at 12 V starts to look unwieldy, that is the signal to step up to 24 V or 48 V, provided the inverter, charger and BMS all match the higher voltage.
What each input means
Stored energy in watt-hours is the energy target you need the battery to hold — from a load list, a solar sizing calculation or a daily consumption figure. A battery rated at 1,200 Wh can theoretically provide 1,200 W for one hour, 600 W for two hours, 100 W for twelve hours or 50 W for twenty-four hours, before losses and discharge limits are considered.
Nominal battery voltage is the voltage of the system you will build: 12, 24 or 48 V as a class, or the exact nominal voltage of your pack. A single LiFePO4 cell is commonly calculated at 3.2 V nominal and a single Li-ion or LiPo cell at 3.7 V nominal; complete packs may be listed as 12, 24, 48 or 51.2 V depending on chemistry and series cell count.
Use nominal voltage, not charge voltage, for this conversion. General energy calculations normally use nominal voltage, not maximum charging voltage or fully charged voltage. A 12 V LiFePO4 battery may charge above 14 V, but its energy is calculated at 12.8 V nominal. A second Wh to Ah Calculator scenario can reveal whether that difference matters.
Reading the result — and its limits
The workbench gives nominal capacity. Real designs must add depth of discharge, reserve capacity and system losses on top, as the worked example shows. A battery used to 80 percent depth of discharge has 20 percent remaining reserve; used to 50 percent, half its capacity is left. Lithium batteries often allow deeper discharge than lead-acid, but the recommended limit still depends on manufacturer, chemistry, BMS, warranty, temperature and cycle-life goal.
The most common mistake is comparing Ah across voltages. A 100 Ah 12 V battery and a 100 Ah 48 V battery do not store the same energy — 1,200 Wh against 4,800 Wh — so an Ah figure without its voltage is meaningless. The second mistake is using charge voltage instead of nominal voltage, which understates the amp-hours you need. Use Wh to Ah Calculator to examine the numbers, not to override a manufacturer limit.
The third mistake is forgetting that the result is a capacity, not a shopping list. Four 12 V 100 Ah batteries in series create a 48 V 100 Ah bank at 4,800 Wh, and the same four in parallel create a 12 V 400 Ah bank, also 4,800 Wh. Both store the same nominal energy but behave differently electrically, and the 48 V bank delivers the same power with much lower current.
The calculator cannot approve an installation. Charger profile, BMS current limits, cable size, fusing and ventilation must agree with each other and with the manufacturer's documentation. A correct conversion on this page says nothing about whether the wiring is safe.
Sources and verification status
Author: Saqib Jillani · Reviewer: lithiumbattery.info Editorial Team
Every conversion on this page is arithmetic from the inputs stated beside it — watt-hours ÷ nominal volts — and every figure can be reworked with a pocket calculator. The nominal voltages (3.2 V LiFePO4; 3.7 V Li-ion and LiPo; 12, 24, 48 and 51.2 V packs) are the standard conventions used across this site's battery guides; a named cell datasheet citation is still to be added. The 80 percent depth-of-discharge and 90 percent inverter-efficiency figures in the worked example are illustrative planning values, not measurements. For background on how batteries store energy, see the U.S. Department of Energy battery reference linked below.