What this calculator does
This calculator converts a battery's amp-hour rating into watt-hours using the battery voltage. Enter the capacity in amp-hours and the nominal voltage, and the workbench returns the stored energy in watt-hours, with the same figure in kilowatt-hours alongside it.
Short answer: watt-hours = amp-hours × volts. A 100 Ah battery at 12 V stores 100 × 12 = 1,200 Wh, while a 100 Ah battery at 48 V stores 100 × 48 = 4,800 Wh. Both hold 100 amp-hours of charge, but the 48 V battery stores four times as much energy because its voltage is four times higher.
That is why watt-hours are the better unit for comparing batteries across system voltages. Solar loads are measured in watt-hours or kilowatt-hours per day, appliances are rated in watts, and runtime is watt-hours divided by watts — so converting Ah to Wh puts the battery on the same scale as everything it has to power. The practical value of Battery Ah to Wh Calculator depends on the accuracy of those inputs.
The formulas behind the result
One formula does the work: Wh = Ah × V. The workbench defaults are 100 Ah and 12.8 V, giving 100 × 12.8 = 1,280 Wh. Divide by 1,000 for kilowatt-hours: 1,280 Wh is 1.28 kWh, and 9,600 Wh is 9.6 kWh.
The formula also explains series and parallel banks. Two 12 V 100 Ah batteries in series become 24 V 100 Ah, which is 2,400 Wh. Four in series become 48 V 100 Ah, or 4,800 Wh. Two in parallel become 12 V 200 Ah, which is also 2,400 Wh — the same energy, delivered at different voltage and current. A cautious interpretation of Battery Ah to Wh Calculator includes the relevant operating limits.
Nominal energy is only the starting point. Usable energy applies the depth of discharge you plan to use, and AC energy applies inverter efficiency on top. A 100 Ah 12 V battery has 1,200 Wh nominal; at 90 percent usable capacity that is 1,200 × 0.90 = 1,080 Wh, and through a 90 percent efficient inverter it is 1,080 × 0.90 = 972 Wh of usable AC energy.
Runtime follows from the same number: hours = Wh ÷ load watts. A 1,200 Wh battery could theoretically run a 100 W load for 1,200 ÷ 100 = 12 hours before losses and reserve limits. With the usable figure above, the same load runs for 972 ÷ 100 = 9.7 hours — the gap between the label calculation and the realistic one.
Worked example: a 100 Ah battery at 12 V and at 48 V
Take the workbench defaults — 100 Ah at 12.8 V — and the same capacity at the other system voltages, so the effect of voltage is visible in one table. The first three rows are the workbench calculation itself; the last two rows apply the usable-capacity and inverter steps from the section above.
| Step | Calculation | Result |
|---|---|---|
| Nominal energy at 12.8 V | 100 × 12.8 | 1,280 Wh (1.28 kWh) |
| Nominal energy at 12 V | 100 × 12 | 1,200 Wh (1.2 kWh) |
| Nominal energy at 48 V | 100 × 48 | 4,800 Wh (4.8 kWh) |
| Usable at 90% depth of discharge | 1,200 × 0.90 | 1,080 Wh |
| Usable AC at 90% inverter efficiency | 1,080 × 0.90 | 972 Wh |
The 48 V row is the lesson: the same 100 Ah stores four times the energy at 48 V as at 12 V, and a 48 V bank delivers the same power at about one-quarter of the current of a 12 V bank. That is why larger inverter systems are usually built at 48 V — lower current means smaller cables, less voltage drop and less heat.
A daily-load check shows how the number is used. If a refrigerator uses 800 Wh per day, lights 300 Wh and electronics 500 Wh, the total is 1,600 Wh per day. One 12 V 100 Ah battery holds about 1,200 Wh nominal, so it cannot cover the whole day once losses and reserves are included — the load list, not the battery label, decides the bank size. Record these assumptions whenever you use Battery Ah to Wh Calculator with another system.
Days of autonomy multiply the requirement. A 3,000 Wh daily load with two days of autonomy needs about 6,000 Wh of usable storage, and at 90 percent usable capacity the nominal bank must be larger than 6,000 Wh. The workbench gives the nominal figure; autonomy and usable share are planning decisions you add on top.
Common Ah to Wh conversions at a glance
The table below converts the battery sizes readers ask about most. Voltages are nominal pack voltages: 12.8 V, 25.6 V and 51.2 V are the 4-series, 8-series and 16-series LiFePO4 packs sold as 12 V, 24 V and 48 V systems. Every figure is amp-hours × volts. This is the uncertainty that a Battery Ah to Wh Calculator worksheet should make visible.
| Battery | Nominal energy | Energy in kWh |
|---|---|---|
| 12 V, 100 Ah | 1,200 Wh | 1.2 kWh |
| 12.8 V, 100 Ah (LiFePO4) | 1,280 Wh | 1.28 kWh |
| 24 V, 100 Ah | 2,400 Wh | 2.4 kWh |
| 25.6 V, 100 Ah (LiFePO4) | 2,560 Wh | 2.56 kWh |
| 48 V, 100 Ah | 4,800 Wh | 4.8 kWh |
| 51.2 V, 100 Ah (LiFePO4) | 5,120 Wh | 5.12 kWh |
| 48 V, 200 Ah | 9,600 Wh | 9.6 kWh |
The 51.2 V row explains a common product label: a 100 Ah 51.2 V LiFePO4 server-rack battery stores 5,120 Wh, which is why many 48 V class LiFePO4 batteries are advertised as 5 kWh batteries. The seller uses the system class voltage for the name and the exact nominal voltage for the energy.
Note also that a 100 Ah bank at 48 V holds the same nominal energy as four 100 Ah batteries at 12 V in series — 4,800 Wh either way. Series and parallel change voltage and current, not total stored energy, as long as the batteries are identical and connected correctly.
What each input means
Battery capacity in amp-hours is the charge the battery is rated to deliver under the manufacturer's stated conditions. Common values are 50, 100, 200 and 300 Ah. A battery rated at 100 Ah can theoretically deliver 100 A for one hour, 10 A for 10 hours or 5 A for 20 hours under ideal test conditions.
Nominal voltage is the battery's rated voltage, not its full-charge voltage. A single LiFePO4 cell is around 3.2 V nominal, while a common Li-ion cell is 3.6 V to 3.7 V nominal. A 12 V LiFePO4 battery may charge above 14 V and a 51.2 V pack above 56 V, but the energy calculation uses the nominal figure.
For a bank, enter the nominal voltage of the complete bank, not of one battery in it. Four 12 V batteries in series are a 48 V bank; the same four in parallel are still a 12 V bank with four times the amp-hours. Either way the workbench needs the bank voltage and the bank amp-hours together. A second Battery Ah to Wh Calculator scenario can reveal whether that difference matters.
Reading the result — and its limits
The workbench shows nominal watt-hours. It does not apply depth of discharge, inverter efficiency or reserve margins — those are planning decisions, and the article shows how to apply them by hand. Lithium batteries often allow deeper discharge than lead-acid, but the exact limit depends on chemistry, manufacturer recommendations and BMS programming.
The two most common mistakes are comparing Ah without voltage and assuming all 12 V batteries are identical. A 100 Ah 12 V battery is not equal in energy to a 100 Ah 48 V battery, and a 12 V label can hide different chemistries and nominal voltages — 12 V, 12.8 V and other values all appear on the market. Check the datasheet voltage, not the class label. Use Battery Ah to Wh Calculator to examine the numbers, not to override a manufacturer limit.
Higher voltage also changes the electrical design, not just the energy number. For the same inverter power, a 48 V bank draws about one-quarter of the current of a 12 V bank, which is why larger systems use higher voltage — but the batteries, BMS, charger and inverter must all match the chosen voltage, and mixing incompatible batteries in a bank is a fault, not a shortcut.
The calculator cannot approve an installation. Charger profile, BMS current limits, cable size, fusing and ventilation must agree with each other and with the manufacturer's documentation. A correct conversion on this page says nothing about whether the wiring is safe.
Sources and verification status
Author: Saqib Jillani · Reviewer: lithiumbattery.info Editorial Team
Every conversion on this page is arithmetic from the inputs stated beside it — amp-hours × nominal volts — and every figure can be reworked with a pocket calculator. The nominal voltages (3.2 V LiFePO4; 3.6–3.7 V Li-ion; 12.8, 25.6 and 51.2 V packs) are the standard conventions used across this site's battery guides; a named cell datasheet citation is still to be added. The 90 percent usable-capacity and 90 percent inverter-efficiency figures in the worked example are illustrative planning values, not measurements — use the limits from your own battery and inverter datasheets when they matter. For background on how batteries store energy, see the U.S. Department of Energy battery reference linked below.