What this calculator does
This calculator converts stored energy into the amp-hour rating a battery needs at a given voltage. Enter the energy in kilowatt-hours and the nominal voltage, and the workbench returns amp-hours. The conversion matters because batteries are sold in amp-hours at a stated voltage, while household and solar planning is usually done in kilowatt-hours.
Short answer: amp-hours = kilowatt-hours × 1,000 ÷ volts. A 10 kWh battery at 48 V is 10 × 1,000 ÷ 48 = 208.3 Ah, while the same 10 kWh at 12 V is 10 × 1,000 ÷ 12 = 833.3 Ah. The energy is identical; the amp-hour rating is not, because the same energy is stored at a different voltage.
The workbench defaults show the conversion at its most familiar: 1.28 kWh at 12.8 V is exactly 100 Ah, the rating of the common 12 V LiFePO4 battery. If that equivalence feels surprising, run the steps in the worked example below — the arithmetic is the whole page. The practical value of kWh to Ah Calculator depends on the accuracy of those inputs. A cautious interpretation of kWh to Ah Calculator includes the relevant operating limits.
That is the mistake this page prevents: comparing amp-hours across voltages. A 200 Ah battery at 12 V stores far less energy than a 200 Ah battery at 48 V, and a 10 kWh bank does not have one fixed amp-hour rating. Always convert through watt-hours before comparing two batteries.
The formulas behind the result
Two steps cover the whole conversion, and the workbench does both. All voltages here are nominal pack voltages — 12 V, 24 V, 48 V or 51.2 V — not full-charge voltages.
Step 1: kilowatt-hours to watt-hours. Wh = kWh × 1,000. So 10 kWh equals 10,000 Wh, and the workbench default of 1.28 kWh equals 1,280 Wh.
Step 2: watt-hours to amp-hours. Ah = Wh ÷ V. The default case is 1,280 Wh ÷ 12.8 V = 100 Ah, which is why the workbench loads with 1.28 kWh and 12.8 V: it is the familiar 12.8 V, 100 Ah battery.
Combined: Ah = kWh × 1,000 ÷ V. A 5 kWh battery at 12 V is 5 × 1,000 ÷ 12 = 416.7 Ah. A 20 kWh bank at 51.2 V is 20 × 1,000 ÷ 51.2 = 390.6 Ah. Run the conversion backwards to check: amp-hours × volts ÷ 1,000 must return the kilowatt-hours you started with.
Usable energy is a separate step the workbench does not take. A 10 kWh battery at 90% usable depth of discharge provides about 9 kWh before inverter losses, and at 90% inverter efficiency the usable AC energy is about 8.1 kWh. If your load target is 10 kWh of usable AC energy, the nominal bank must be larger than 10 kWh.
Worked example: 1.28 kWh at 12.8 V
Take the workbench as it loads: 1.28 kWh of energy and a 12.8 V nominal voltage. The steps below replay the default case, then the same energy at the other common system voltages. Record these assumptions whenever you use kWh to Ah Calculator with another system. This is the uncertainty that a kWh to Ah Calculator worksheet should make visible.
| Step | Calculation | Result |
|---|---|---|
| Energy in watt-hours | 1.28 kWh × 1,000 | 1,280 Wh |
| Amp-hours at 12.8 V | 1,280 ÷ 12.8 | 100 Ah |
| Check: back to kWh | 100 × 12.8 ÷ 1,000 | 1.28 kWh |
| Same energy at 48 V | 1,280 ÷ 48 | 26.7 Ah |
| 10 kWh at 48 V | 10 × 1,000 ÷ 48 | 208.3 Ah |
| 10 kWh at 12 V | 10 × 1,000 ÷ 12 | 833.3 Ah |
The last two rows are the point of the page. Ten kilowatt-hours needs about 208 Ah at 48 V but about 833 Ah at 12 V — four times the amp-hours for the same energy. That is why larger storage systems use 48 V or 51.2 V banks: the current stays manageable, the cables stay thinner, and the inverter runs more efficiently.
A home example: if your home uses 20 kWh per day and you want one day of backup, start with a 20 kWh storage target. At 48 V that is about 416 Ah; at 51.2 V it is about 391 Ah. Those values help when comparing modules sold as 100 Ah, 200 Ah or 280 Ah units — a 51.2 V, 100 Ah module stores about 5.12 kWh, so four of them provide about 20.48 kWh nominal.
kWh to amp-hours at the common voltages
The table below converts four common storage sizes at the four common system voltages. Every cell is kilowatt-hours × 1,000 ÷ volts, so any figure can be checked by hand. Use the nominal voltage of your bank, not its full-charge voltage.
| Storage | 12 V | 24 V | 48 V | 51.2 V |
|---|---|---|---|---|
| 5 kWh | 416.7 Ah | 208.3 Ah | 104.2 Ah | 97.7 Ah |
| 10 kWh | 833.3 Ah | 416.7 Ah | 208.3 Ah | 195.3 Ah |
| 20 kWh | 1,666.7 Ah | 833.3 Ah | 416.7 Ah | 390.6 Ah |
| 50 kWh | 4,166.7 Ah | 2,083.3 Ah | 1,041.7 Ah | 976.6 Ah |
Two patterns are worth noting. Doubling the voltage halves the amp-hours for the same energy, and a 51.2 V LiFePO4 bank needs slightly fewer amp-hours than a 48 V bank for the same kilowatt-hours. Neither change alters the stored energy — only the rating the battery carries on its label.
What each input means
Energy in kilowatt-hours is the storage target, in kWh. It can be a battery's rated energy, a daily household load, or a backup target such as 10 kWh for one day. One kilowatt-hour means 1,000 watts used for one hour, so a home using 10 kWh per day uses about 10,000 Wh of electrical energy per day.
Nominal voltage is the rated voltage of the battery bank, in volts. Common options are 12 V for small systems, 24 V for medium systems, and 48 V or 51.2 V for larger inverter systems and LiFePO4 server-rack batteries. Four 12 V, 100 Ah batteries in series become a 48 V, 100 Ah bank with about 4,800 Wh; the same four in parallel become a 12 V, 400 Ah bank with the same 4,800 Wh. Series changes voltage, parallel changes amp-hours, energy stays the same.
Module arithmetic is where the conversion pays off. A 51.2 V, 100 Ah module stores about 5.12 kWh, so four modules provide about 20.48 kWh nominal. If your target is 20 kWh, four modules cover it on paper; if your target is 20 kWh usable, you need a fifth module or a deeper usable window, because the nominal figure is not the delivered figure. A second kWh to Ah Calculator scenario can reveal whether that difference matters. Use kWh to Ah Calculator to examine the numbers, not to override a manufacturer limit.
The workbench has no depth-of-discharge or efficiency input, and its answer is nominal amp-hours, not usable amp-hours. A lithium battery may allow deep discharge, but using 100% of nominal capacity every cycle may not be ideal for long-term life, so treat the result as the size of the bank to buy, then apply your usable window on top of it.
Reading the result — and its limits
Treat the result as a nominal rating, not a delivered-energy promise. A battery listed as 10 kWh does not always deliver 10 kWh to AC loads: depth of discharge, inverter efficiency, temperature and reserve settings all reduce what arrives at the load. If your daily load is 6 kWh and you want two days of autonomy, you need about 12 kWh of usable storage before losses and reserves, which means a larger nominal bank.
The result also assumes the voltage you entered stays fixed. Real battery voltage sags under load and rises while charging, so the amp-hours delivered over a full discharge differ slightly from the nominal division. For sizing that is a second-order effect; for a precise energy audit, measure watt-hours directly rather than converting from amp-hours.
Check the voltage you enter against the battery label, not the system name. A battery sold as a 48 V battery may be a 51.2 V LiFePO4 pack, and using 48 V in the division overstates the amp-hours by about 7%: 10,000 ÷ 48 = 208.3 Ah against 10,000 ÷ 51.2 = 195.3 Ah. The difference is small, but it is the difference between ordering the right module and ordering one too many.
Finally, do not size a bank to the exact calculated minimum. Module sizes are discrete — 100 Ah, 200 Ah, 280 Ah — so round up to the next available module, and confirm the parallel and series rules for your battery model with the manufacturer before ordering.
Sources and verification status
Author: Saqib Jillani · Reviewer: lithiumbattery.info Editorial Team
The formulas and worked numbers on this page are arithmetic from the inputs stated beside them — every figure can be reworked with a pocket calculator. The module figures (51.2 V, 100 Ah = 5.12 kWh; four modules = 20.48 kWh) follow from the same formula. The 90% usable depth-of-discharge and 90% inverter-efficiency figures are planning conventions carried over from this site's sizing guides, not measurements, and the page labels them as such. For background on how batteries store energy, see the U.S. Department of Energy battery reference linked below. The result from kWh to Ah Calculator should be compared with the equipment specification. A follow-up using kWh to Ah Calculator should change only one input at a time.